Electrical Services
Following tests are to be carried out as per IS: 325.
- AC hi – pot test at 2.0 kv r.m.s. for 1 minute.
- IR test at 1.0 kv dc before and after hv test.
- Winding resistance test.
- Impedance test by use of 1 phase and 3 phase low voltage ac supply.
- No load test run.(UP TO 50-HP )
- Space heater test.
- Vibration testing.
- Motor checker for inductance testing.
Guarantee:
Rewound motor will be guaranteed for ‘B’ class insulation 6 months & ‘F’ class insulation 12 months from the date of dispatch against the defect of material and workmanship only.